{"schema":"/api/v1/schema/cve.json","api_version":"1","id":"CVE-2018-4839","published":"2018-03-08T17:29:00.257000Z","last_modified":"2026-06-17T01:59:08.720000Z","status":"Modified","cvss":{"version":"3.0","score":5.3,"severity":"MEDIUM","vector":"CVSS:3.0/AV:N/AC:H/PR:L/UI:N/S:U/C:H/I:N/A:N","source":"nvd@nist.gov","primary":true},"auth":true,"cwes":["CWE-326"],"cpes":[{"criteria":"cpe:2.3:o:siemens:siprotec_compact_7sj80_firmware:*:*:*:*:*:*:*:*","part":"o","vendor":"siemens","product":"siprotec_compact_7sj80_firmware","version_end_excluding":"4.77"},{"criteria":"cpe:2.3:o:siemens:siprotec_compact_7sk80_firmware:*:*:*:*:*:*:*:*","part":"o","vendor":"siemens","product":"siprotec_compact_7sk80_firmware","version_end_excluding":"4.77"},{"criteria":"cpe:2.3:o:siemens:siprotec_4_7sj66_firmware:*:*:*:*:*:*:*:*","part":"o","vendor":"siemens","product":"siprotec_4_7sj66_firmware","version_end_excluding":"4.30"},{"criteria":"cpe:2.3:o:siemens:digsi_4:*:*:*:*:*:*:*:*","part":"o","vendor":"siemens","product":"digsi_4","version_end_excluding":"4.92"},{"criteria":"cpe:2.3:o:siemens:en100_ethernet_module_iec_104_firmware:-:*:*:*:*:*:*:*","part":"o","vendor":"siemens","product":"en100_ethernet_module_iec_104_firmware"},{"criteria":"cpe:2.3:o:siemens:en100_ethernet_module_dnp3_firmware:-:*:*:*:*:*:*:*","part":"o","vendor":"siemens","product":"en100_ethernet_module_dnp3_firmware"},{"criteria":"cpe:2.3:o:siemens:en100_ethernet_module_modbus_tcp_firmware:-:*:*:*:*:*:*:*","part":"o","vendor":"siemens","product":"en100_ethernet_module_modbus_tcp_firmware"},{"criteria":"cpe:2.3:o:siemens:en100_ethernet_module_profinet_io_firmware:-:*:*:*:*:*:*:*","part":"o","vendor":"siemens","product":"en100_ethernet_module_profinet_io_firmware"},{"criteria":"cpe:2.3:o:siemens:en100_ethernet_module_iec_61850_firmware:*:*:*:*:*:*:*:*","part":"o","vendor":"siemens","product":"en100_ethernet_module_iec_61850_firmware","version_end_excluding":"4.30"}],"cpes_truncated":false,"vendors":["siemens"],"products":["siemens/siprotec_compact_7sj80_firmware","siemens/siprotec_compact_7sk80_firmware","siemens/siprotec_4_7sj66_firmware","siemens/digsi_4","siemens/en100_ethernet_module_iec_104_firmware","siemens/en100_ethernet_module_dnp3_firmware","siemens/en100_ethernet_module_modbus_tcp_firmware","siemens/en100_ethernet_module_profinet_io_firmware","siemens/en100_ethernet_module_iec_61850_firmware"],"cat":"firmware","platform":"appliance","eol":false,"packages":[],"severity":"medium","priority_score":32,"links":{"html_es":"/es/cve/CVE-2018-4839/","html_en":"/en/cve/CVE-2018-4839/","nvd":"https://nvd.nist.gov/vuln/detail/CVE-2018-4839","cve_org":"https://www.cve.org/CVERecord?id=CVE-2018-4839"},"untrusted":{"vendor_name":"Siemens","product_name":"Siprotec Compact 7sj80 Firmware","desc_en":"A vulnerability has been identified in DIGSI 4 (All versions < V4.92), EN100 Ethernet module DNP3 variant (All versions < V1.05.00), EN100 Ethernet module IEC 104 variant (All versions), EN100 Ethernet module IEC 61850 variant (All versions < V4.30), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module PROFINET IO variant (All versions), Other SIPROTEC 4 relays (All versions), Other SIPROTEC Compact relays (All versions), SIPROTEC 4 7SD80 (All versions < V4.70), SIPROTEC 4 7SJ61 (All versions < V4.96), SIPROTEC 4 7SJ62 (All versions < V4.96), SIPROTEC 4 7SJ64 (All versions < V4.96), SIPROTEC 4 7SJ66 (All versions < V4.30), SIPROTEC Compact 7SJ80 (All versions < V4.77), SIPROTEC Compact 7SK80 (All versions < V4.77). An attacker with local access to the engineering system or in a privileged network position and able to obtain certain network traffic could possibly reconstruct access authorization passwords.","affected":[{"untrusted_vendor":"Siemens","untrusted_product":"DIGSI 4"},{"untrusted_vendor":"Siemens","untrusted_product":"EN100 Ethernet module DNP3 variant"},{"untrusted_vendor":"Siemens","untrusted_product":"EN100 Ethernet module IEC 104 variant"},{"untrusted_vendor":"Siemens","untrusted_product":"EN100 Ethernet module IEC 61850 variant"},{"untrusted_vendor":"Siemens","untrusted_product":"EN100 Ethernet module Modbus TCP variant"},{"untrusted_vendor":"Siemens","untrusted_product":"EN100 Ethernet module PROFINET IO variant"},{"untrusted_vendor":"Siemens","untrusted_product":"Other SIPROTEC 4 relays"},{"untrusted_vendor":"Siemens","untrusted_product":"Other SIPROTEC Compact relays"},{"untrusted_vendor":"Siemens","untrusted_product":"SIPROTEC 4 7SD80"},{"untrusted_vendor":"Siemens","untrusted_product":"SIPROTEC 4 7SJ61"},{"untrusted_vendor":"Siemens","untrusted_product":"SIPROTEC 4 7SJ62"},{"untrusted_vendor":"Siemens","untrusted_product":"SIPROTEC 4 7SJ64"},{"untrusted_vendor":"Siemens","untrusted_product":"SIPROTEC 4 7SJ66"},{"untrusted_vendor":"Siemens","untrusted_product":"SIPROTEC Compact 7SJ80"},{"untrusted_vendor":"Siemens","untrusted_product":"SIPROTEC Compact 7SK80"}],"references":[{"url":"https://cert-portal.siemens.com/productcert/pdf/ssa-203306.pdf","tags":["Patch","Vendor Advisory"]},{"url":"https://ics-cert.us-cert.gov/advisories/ICSA-18-067-01","tags":["Third Party Advisory","US Government Resource"]}]}}