CVE-2011-3322Scadatec Procyon Scada
Critical 10.0 No auth neededHigh EPSS
Follow: this CVE · Scadatec · Scadatec Procyon Scada We alert you by email or Slack (account required).
- Priority
- 81
- CVSS 2.0
- 10.0
- EPSS
- 64.7% probability of exploitation in 30 days · percentile 99
- Auth required
- No
- Published
- Sep 15, 2011
- Updated
- Jun 16, 2026
- Category
- Application · Cross-platform
- Weakness (CWE)
- CWE-119
- Vector
AV:N/AC:L/Au:N/C:C/I:C/A:C
What happens
Core Server HMI Service (Coreservice.exe) in Scadatec Limited Procyon SCADA 1.06, and other versions before 1.14, allows remote attackers to cause a denial of service (crash) and possibly execute arbitrary code via a long password to the Telnet (TCP/23) port, which triggers an out-of-bounds read or write, leading to a stack-based buffer overflow.
What to do
- Apply the vendor's security update for Procyon Scada.
- It can be exploited without authentication: if you cannot patch now, restrict Internet access to the affected service.
Affected products (CPE)
| Vendor | Product | Versions |
|---|---|---|
| scadatec | procyon_scada | 1.06 |
| scadatec | procyon_scada | 1.13 |
Official sources
References
Links published by the sources. Open them with care.
- osvdb.org
- secunia.com Vendor Advisory
- securityreason.com
- www.exploit-db.com Exploit
- www.securityfocus.com
- www.stratsec.net
- www.uscert.gov US Government Resource
- exchange.xforce.ibmcloud.com