CVE-2018-13813Siemens Simatic Hmi Comfort Panels Firmware
High 8.1 No auth needed
Follow: this CVE · Siemens · Siemens Simatic Hmi Comfort Panels Firmware We alert you by email or Slack (account required).
- Priority
- 64
- CVSS 3.0
- 8.1
- EPSS
- 1.7% probability of exploitation in 30 days · percentile 77
- Auth required
- No
- Published
- Dec 13, 2018
- Updated
- Jun 17, 2026
- Category
- Firmware · Network appliance
- Weakness (CWE)
- CWE-601
- Vector
CVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:N
What happens
A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V15 Update 4), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V15 Update 4), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V15 Update 4), SIMATIC WinCC Runtime Advanced (All versions < V15 Update 4), SIMATIC WinCC Runtime Professional (All versions < V15 Update 4), SIMATIC WinCC (TIA Portal) (All versions < V15 Update 4), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) (All versions). The webserver of affected HMI devices may allow URL redirections to untrusted websites. An attacker must trick a valid user who is authenticated to the device into clicking on a malicious link to exploit the vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
What to do
- Apply the vendor's security update for Simatic Hmi Comfort Panels Firmware.
- It can be exploited without authentication: if you cannot patch now, restrict Internet access to the affected service.
Affected products (CPE)
| Vendor | Product | Versions |
|---|---|---|
| siemens | simatic_hmi_comfort_panels_firmware | ≤ 15.0 |
| siemens | simatic_hmi_comfort_outdoor_panels_firmware | ≤ 15.0 |
| siemens | simatic_hmi_ktp_mobile_panels_ktp400f_firmware | ≤ 15.0 |
| siemens | simatic_hmi_ktp_mobile_panels_ktp700_firmware | ≤ 15.0 |
| siemens | simatic_hmi_ktp_mobile_panels_ktp700f_firmware | ≤ 15.0 |
| siemens | simatic_hmi_ktp_mobile_panels_ktp900_firmware | ≤ 15.0 |
| siemens | simatic_hmi_ktp_mobile_panels_ktp900f_firmware | ≤ 15.0 |
| siemens | simatic_wincc_(tia_portal) | ≤ 15.0 |
| siemens | simatic_wincc_runtime | ≤ 15.0 |
| siemens | simatic_wincc_runtime | ≤ 15.0 |
| siemens | simatic_hmi_tp_firmware | all |
| siemens | simatic_hmi_mp_firmware | all |
| siemens | simatic_hmi_op_firmware | all |
Official sources
References
Links published by the sources. Open them with care.
- www.securityfocus.com Third Party Advisory VDB Entry
- cert-portal.siemens.com Vendor Advisory