Amenazas en vivo

Todas las CVE / Siemens

CVE-2018-4844Siemens Simatic Wincc Oa Ui

Media 6.7

Prioridad
40
CVSS 3.1
6.7
EPSS
0.4%
probabilidad de explotación en 30 días · percentil 28
Requiere autenticación
Sí
Publicada
20 mar 2018
Actualizada
17 jun 2026
Categoría
Aplicación · Multiplataforma
Debilidad (CWE)
CWE-284, CWE-269
Vector
CVSS:3.1/AV:A/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:N

Qué pasa

A vulnerability has been identified in SIMATIC WinCC OA UI for Android (All versions < V3.15.10), SIMATIC WinCC OA UI for iOS (All versions < V3.15.10). Insufficient limitation of CONTROL script capabilities could allow read and write access from one HMI project cache folder to other HMI project cache folders within the app's sandbox on the same mobile device. This includes HMI project cache folders of other configured WinCC OA servers. The security vulnerability could be exploited by an attacker who tricks an app user to connect to an attacker-controlled WinCC OA server. Successful exploitation requires user interaction and read/write access to the app's folder on a mobile device. The vulnerability could allow reading data from and writing data to the app's folder. At the time of advisory publication no public exploitation of this security vulnerability was known. Siemens confirms the security vulnerability and provides mitigations to resolve the security issue.

Texto original de NVD, en inglés. La traducción y el resumen en español llegan pronto.

Qué hacer

  1. Aplica la actualización de seguridad del fabricante para Simatic Wincc Oa Ui.

Productos afectados (CPE)

FabricanteProductoVersiones
siemenssimatic_wincc_oa_ui< 3.15.10
siemenssimatic_wincc_oa_ui< 3.15.10

Fuentes oficiales

Referencias

Enlaces publicados por las fuentes. Ábrelos con criterio.