Amenazas en vivo
VulnFox

Todas las CVE / Automationdirect

CVE-2020-10921Automationdirect C-more Hmi Ea9 Firmware

Crítica 9.8 Sin autenticación

Prioridad
74
CVSS 3.1
9.8
EPSS
—
Requiere autenticación
No
Publicada
23 jul 2020
Actualizada
17 jun 2026
Categoría
Firmware · Equipo de red
Debilidad (CWE)
CWE-306
Vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Qué pasa

This vulnerability allows remote attackers to issue commands on affected installations of C-MORE HMI EA9 Firmware version 6.52 touch screen panels. Authentication is not required to exploit this vulnerability. The specific flaw exists within the EA-HTTP.exe process. The issue results from the lack of authentication prior to allowing alterations to the system configuration. An attacker can leverage this vulnerability to issue commands to the physical equipment controlled by the device. Was ZDI-CAN-10482.

Texto original de NVD, en inglés. La traducción y el resumen en español llegan pronto.

Qué hacer

  1. Aplica la actualización de seguridad del fabricante para C-more Hmi Ea9 Firmware.
  2. Se explota sin autenticación: si no puedes parchear ya, limita el acceso desde Internet al servicio afectado.

Productos afectados (CPE)

FabricanteProductoVersiones
automationdirectc-more_hmi_ea9_firmware6.52

Fuentes oficiales

Referencias

Enlaces publicados por las fuentes. Ábrelos con criterio.