Live threats

All CVEs / Siemens

CVE-2016-4785Siemens Siprotec Firmware

Medium 5.3 No auth needed

Priority
47
CVSS 3.0
5.3
EPSS
2.7%
probability of exploitation in 30 days · percentile 87
Auth required
No
Published
May 31, 2016
Updated
Jun 17, 2026
Category
Firmware · Network appliance
Weakness (CWE)
CWE-200
Vector
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N

What happens

A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02. The integrated web server (port 80/tcp) of the affected devices could allow remote attackers to obtain a limited amount of device memory content if network access was obtained. This vulnerability only affects EN100 Ethernet module included in SIPROTEC4 and SIPROTEC Compact devices.

Original NVD text.

What to do

  1. Apply the vendor's security update for Siprotec Firmware.
  2. It can be exploited without authentication: if you cannot patch now, restrict Internet access to the affected service.

Affected products (CPE)

VendorProductVersions
siemenssiprotec_firmware4.26
siemenssiprotec_firmwareall

Official sources

References

Links published by the sources. Open them with care.