Amenazas en vivo
VulnFox

Todas las CVE / Siemens

CVE-2016-4785Siemens Siprotec Firmware

Media 5.3 Sin autenticación

Prioridad
47
CVSS 3.0
5.3
EPSS
—
Requiere autenticación
No
Publicada
31 may 2016
Actualizada
17 jun 2026
Categoría
Firmware · Equipo de red
Debilidad (CWE)
CWE-200
Vector
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N

Qué pasa

A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02. The integrated web server (port 80/tcp) of the affected devices could allow remote attackers to obtain a limited amount of device memory content if network access was obtained. This vulnerability only affects EN100 Ethernet module included in SIPROTEC4 and SIPROTEC Compact devices.

Texto original de NVD, en inglés. La traducción y el resumen en español llegan pronto.

Qué hacer

  1. Aplica la actualización de seguridad del fabricante para Siprotec Firmware.
  2. Se explota sin autenticación: si no puedes parchear ya, limita el acceso desde Internet al servicio afectado.

Productos afectados (CPE)

FabricanteProductoVersiones
siemenssiprotec_firmware4.26
siemenssiprotec_firmwaretodas

Fuentes oficiales

Referencias